Objects For Setpoint Temperature Limit - Gira KNX 2139 00 Product Documentation

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Setpoint temperature limit, cooling
Limit from an outdoor temperature of
This parameter defines the outdoor temperature at which limitation of the setpoint
temperature becomes active in cooling mode.
Difference between setpoint temperature
and outdoor temperature of
This parameter defines the maximum difference between the setpoint temperature in
Comfort mode and the outdoor temperature with an active setpoint temperature limit.
This parameter is visible only if setpoint temperature monitoring is enabled. How-
ever, this is only if the parameter "Setpoint temperature limit in cooling operation" is
then set to "Only difference to outdoor temperature" or "Max. setpoint temperature
and difference to outdoor temperature".
Maximum setpoint temperature
This parameter defines the maximum setpoint temperature in Comfort mode with an
active setpoint temperature limit.
This parameter is visible only if setpoint temperature monitoring is enabled. How-
ever, this is only if the parameter "Setpoint temperature limit in cooling operation" is
then set to "Only max. setpoint temperature" or "Max. setpoint temperature and dif-
ference to outdoor temperature".
Activation
A setpoint limit enabled in the ETS can be activated or deactivated as necessary us-
ing a 1-bit object. For this, this parameter can be set to "Yes". In this case, the con-
troller only takes the setpoint limit into account, if it has been enabled via the object
"Cooling setpoint temperature limit" ("1" telegram). If the limitation is not enabled ("0"
telegram), the cooling setpoint temperatures are not limited.
This parameter is visible only if setpoint temperature monitoring is enabled.

10.9.2 Objects for setpoint temperature limit

Object no.
364, 414,
464, 514,
564, 614,
664, 714,
764, 814,
864, 914
1-bit object for activation or deactivation of a setpoint temperature limit.
"0" = deactivate raising of setpoint
"1" = activate raising of setpoint
If the setpoint limit is permanently activated, the communication object is not visible.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Setpoint temperat-
ure limit - Activate /
Deactivate
20...32...45 °C
1 ...6 ...15 K
20°C...26°C...35°C
via object
permanently active
Name
RTC x - Input
Type
DPT
Flag
1-bit
1,001
C, -, W, -, U
Page 202 of 257