Room temperature controller | Operating mode and setpoints
Object no.
343, 393,
443, 493,
543, 593,
643, 693,
743, 793,
843, 893
2-byte object for the output of the current temperature setpoint. Depending on the
operating mode, the possible range of values is limited by the configured frost pro-
tection and/or heat protection temperature.
The temperature value is always output in the format "°C".
After mains voltage return or an ETS programming operation (controller reset), the
current setpoint temperature is transmitted via this object.
Function: absolute setpoint temperature specification
Object no.
333, 383,
433, 483,
533, 583,
633, 683,
733, 783,
833, 883
2-byte object for external setting of a setpoint for absolute setpoint presetting. De-
pending on the operating mode, the possible range of values is limited by the con-
figured frost protection and/or heat protection temperature. The controller rounds the
temperature values received via the object to 0.1 K.
The temperature value must always be specified in the format "°C".
Function: relative setpoint temperature specification, basic value
Object no.
333, 383,
433, 483,
533, 583,
633, 683,
733, 783,
833, 883
2-byte object for external specification of the basic setpoint for relative setpoint spe-
cification. Depending on the operating mode, the possible range of values is limited
by the configured frost protection and/or heat protection temperature. The controller
rounds the temperature values received irrespective of the configured value of the of
the setpoint shift (0.1 K or 0.5 K).
The temperature value must always be specified in the format "°C".
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Setpoint temperat-
ure - Active operat-
ing mode - Status
Function
Setpoint temperat-
ure - Active operat-
ing mode
Function
Setpoint temperat-
ure - Basic value
Name
RTC x - Output
Name
RTC x - Input
Name
RTC x - Input
Type
DPT
Flag
2 bytes 9,001
C, R, -, T, A
Type
DPT
Flag
2 bytes 9,001
C, -, W, -, U
Type
DPT
Flag
2 bytes 9,001
C, -, W, -, U