Valve outputs | Operating hours counter
Object no.
114, 121,
128, 135,
142, 149
2-byte object to transmit or read out the current counter level of the operating hours
counter of a valve output.
Value range: 0...65,535 hours
If the bus voltage should fail, the value of the communication object is not lost and is
actively transmitted to the bus after bus voltage return or an ETS programming oper-
ation. In the as-delivered state, the value is "0".
This object is only available with the hour counter.
Object no.
115, 122,
129, 136,
143, 150
1-bit object to sign that the operating hours counter has elapsed (forwards counter =
signal value reached / backwards counter = value "0" reached). With a message, the
object value is actively transmitted to the KNX ("1" = message active / "0" = mes-
sage inactive).
If the bus voltage should fail, the value of the communication object is not lost and is
actively transmitted to the bus after bus voltage return or an ETS programming oper-
ation.
Object no.
110, 117,
124, 131,
138, 145
4-byte object for external presetting of a signal value / start value of the operating
hours counter of a valve output.
Value range: 0...2147483647 seconds
This object is only available with the second counter.
Object no.
111, 118,
125, 132,
139, 146
2-byte object for external presetting of a signal value / start value of the operating
hours counter of a valve output.
Value range: 0...65,535 hours
This object is only available with the hour counter.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Operating hours
counter - Meter
reading - Status
Function
Operating hours
counter - Counter
elapsed
Function
Operating hours
counter - Signal
value / Start value
Function
Operating hours
counter - Signal
value / Start value
Name
VO x ... - Output
Name
VO x ... - Output
Name
VO x ... - Input
Name
VO x ... - Input
Type
DPT
Flag
2 bytes 7,007
C, (R), -, T,
A
Type
DPT
Flag
1-bit
1,002
C, (R), -, T,
A
Type
DPT
Flag
4 bytes 13,100 C, (R), W, -,
A
Type
DPT
Flag
2 bytes 7,007
C, (R), W, -,
A