Gira KNX 2139 00 Product Documentation page 230

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Logic functions | Disabling element [Filtering/Time]
Delay for OFF telegrams
Minutes (0...59)
The delay for OFF telegrams is configured here. A delay is only effective if the delay
time is set to greater than "0". Each OFF telegram received at the input re-triggers
the delay time.
Special feature when using the delays: If no telegram is received at the input, a con-
figured delay time (time > 0) acts like an automatic cyclic trigger of the filter. The
most recently received input status is then forwarded to the filter automatically and
repeatedly after the delay has elapsed. This then works according to its configura-
tion and forwards the result to the output of the disabling element. Consequently, the
output then also transmits telegrams depending on the transmission criteria set. If
the cyclical transmission of the output is not desired due to the automatic triggering
of the filter, the transmission criterion should be set to "only transmit if the output
changes".
After bus voltage return or after an ETS programming operation, the delays are
triggered automatically.
Setting the OFF delay time minutes.
Seconds (0...59)
Setting the OFF delay time seconds.
The parameters for the OFF delay are only available if the parameter "Time function"
is set to "only delay OFF telegrams" or "delay ON and OFF telegrams".
Polarity of the disabling object
This parameter defines the polarity of the disabling object.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
0...59
0...10...59
0 = enabled / 1 = disabled
0 =disabled/ 1 = enabled
Page 230 of 257