Gira KNX 2139 00 Product Documentation page 91

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Valve outputs | forced position
Command value (summer)
When forced operation is activated via a 1-bit object, after voltage return or after an
ETS programming operation, it is possible to set the forced command value con-
figured here as the active command value. The command value preset here is only
applied if summer operation is activated.
When the command value of the forced position is recalled, the valve output con-
figured to the command value data formats "Switching (1-bit)" or "Constant (1-byte)
with command value limiting value" is always activated by a constant command
value with pulse width modulation.
Command value (winter)
When forced operation is activated via a 1-bit object, voltage return or after an ETS
programming operation, it is possible to set the forced command value configured
here as the active command value. The command value preset here is only applied
if winter mode is activated.
When the command value of the forced position is recalled, the valve output con-
figured to the command value data formats "Switching (1-bit)" or "Constant (1-byte)
with command value limiting value" is always activated by a constant command
value with pulse width modulation.
Forced position controllable via object
This parameter enables the "Forced position - Activate / Deactivate" object.
Yes: The object "Forced position - Activate / Deactivate" is visible. The forced
position is activated and deactivated via a separate 1-bit object.
No: The configured forced command values are used for the reset behaviour
after voltage return and after ETS programming operation. A forced position
cannot be activated.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
0 %
10 %
...
30 %
...
90 %
100 %
0 %
10 %
...
70 %
...
90 %
100 %
Checkbox (yes / no)
Page 91 of 257