Gira KNX 2139 00 Product Documentation page 192

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Controller status
Object no.
348, 398,
449, 498,
548, 598,
648, 698,
748, 798,
848, 898
1-byte object used by the controller to output the operating mode in the event of
forced position. This object is generally used to enable controller extensions to dis-
play the controller operating mode correctly in the KNX compliant status display.
Therefore this object should be connected with controller extensions if the KNX com-
pliant status feedback is not configured.
After voltage return or an ETS programming operation, the current status is transmit-
ted via this object. This object is only available if the parameter "Status objects - Op-
erating mode" is activated.
Object no.
347, 397,
447, 497,
547, 597,
647, 697,
747, 797,
847, 897
2-byte object that the controller uses to display elementary basic functions in a KNX-
harmonised manner (RHCC).
After voltage return or an ETS programming operation, the current status is transmit-
ted via this object.
Object no.
379, 429,
479, 529,
579, 629,
679, 729,
779, 829,
879, 929
2-byte object that the controller uses to display elementary basic functions in a KNX-
harmonised manner (RTSM).
After voltage return or an ETS programming operation, the current status is transmit-
ted via this object.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Operating mode -
Forced - Status
Function
Controller status
RHCC - KNX-com-
pliant
Function
Controller status
RTSM - KNX-com-
pliant
Name
Controller x - Output 1 bytes 20,102 C, -, -, T, -
Name
RTC x - Output
Name
RTC x - Output
Type
DPT
Flag
Type
DPT
Flag
2 bytes 22,101 C, R, -, T, A
Type
DPT
Flag
1 bytes 21,107 C, R, -, T, A