Gira KNX 2139 00 Product Documentation page 155

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Operating mode and setpoints
Approve change via bus
Here, it is possible to specify if it is possible to change the basic setpoint via the bus.
This parameter is only visible with relative setpoint presetting!
Accept permanently
In addition to specifying individual setpoint temperatures by the ETS or basic set-
point object, the user can shift the basic setpoint in a specific range via a communic-
ation object. Whether a basic setpoint shifting only affects the currently active oper-
ating mode or whether it influences all other setpoint temperatures of the remaining
operating modes is determined by this parameter.
In the "yes" setting, the shift of the basic setpoint carried out affects all operating
modes. The shift is maintained even after a switchover of the operating mode or the
heating/cooling mode or adjusting the basic setpoint.
In the "no" setting, the basic setpoint shift carried out is in effect for only as long as
the operating mode or heating/cooling mode has not changed or the basic setpoint is
maintained. Otherwise the setpoint shift will be reset to "0".
This parameter is only visible with relative setpoint presetting!
Temperature shift via operating mode for relative setpoint presetting
Heating
Standby
The value by which the standby setpoint temperature for heating is lowered com-
pared to the heating comfort temperature.
The parameter is only visible in the "Heating" or "Heating and cooling" operating
mode (if necessary with additional levels) and only with relative setpoint presetting.
Night
The value by which the night temperature for heating is lowered compared to the
heating comfort temperature.
The parameter is only visible in the "Heating" or "Heating and cooling" operating
mode (if necessary with additional levels) and only with relative setpoint presetting.
Frost protection
This parameter specifies the setpoint temperature for frost protection. The parameter
is only visible in "Heating" or "Heating and cooling" operating modes (if necessary
with additional levels).
Cooling
Standby
The value by which the standby setpoint temperature for cooling is raised compared
to the cooling comfort temperature.
The parameter is only visible in the "Heating" or "Heating and cooling" operating
mode (if necessary with additional levels) and only with relative setpoint presetting.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Checkbox (yes / no)
Checkbox (yes / no)
-10...-2...0 K
-10...-4...0 K
7.0 ... 40 °C
0...20...10 K
Page 155 of 257