Heating actuator 6-gang with controller
Table of Contents

Advertisement

Valve outputs | Valve output - General
After ETS programming operation
After an ETS programming operation, the valve outputs perform the configured reac-
tion at this point.
Command value as after voltage return: After an ETS programming operation, the
valve output behaves in the manner defined in the parameter "After bus voltage re-
turn". If the behaviour there is configured to "Command value as before voltage fail-
ure", then that command value is also set after an ETS programming operation
which was active at the time of the last bus voltage failure. An ETS programming op-
eration does not overwrite the saved command value.
Specify command value: The actuator sets the command value preset in the ETS for
the valve output by the following parameter "Command value".
Command value according to forced position: For the valve output, the actuator polls
the command value preset for the forced position, as configured in the ETS. Here,
the active operating mode (summer / winter) is taken into account, providing that a
summer / winter change-over is configured.
Ensure that, in this setting, the forced position function is not executed! The actuator
only polls the command value preset for the forced position.
Command value according to emergency operation: For the valve output, the actu-
ator polls the emergency operation command value, as configured in the ETS. Here,
the active operating mode (summer / winter) is taken into account, providing that a
summer / winter change-over is configured.
Ensure that, in this setting, emergency operation is not executed (as would be the
case if there was a faulty command value found in the course of command value
monitoring)! The actuator only polls the command value preset for emergency oper-
ation.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Command value as after voltage return
Specify command value
Command value according to forced posi-
tion
Command value according to emergency
operation