Logic functions | Disabling element [Filtering/Time]
Filter function
This parameter defines the function of the filter.
ON -> ON / OFF -> OFF: Input telegrams are forwarded to the output unchanged.
Filter deactivated.
ON -> --- / OFF -> OFF: ON telegrams are filtered and not forwarded to the output.
OFF telegrams are forwarded to the output unchanged.
ON -> ON / OFF -> ---: OFF telegrams are filtered and not forwarded to the output.
ON telegrams are forwarded to the output unchanged.
ON -> OFF / OFF -> ON: ON telegrams are converted to OFF telegrams and OFF
telegrams are converted to ON telegrams and forwarded to the output.
ON -> --- / OFF -> ON: ON telegrams are filtered and not forwarded to the output.
OFF telegrams are converted to ON telegrams and forwarded to the output.
ON -> OFF / OFF -> ---: OFF telegrams are filtered and not forwarded to the output.
ON telegrams are converted to OFF telegrams and forwarded to the output.
Transmission criteria
The transmission behaviour of the output can be configured here.
Always transmit when the input is updated: The output transmits the current object
value to the KNX with every telegram that is received at the input. In addition, trans-
mission at the output is repeated if no telegram was received at the input when the
delay times were used and the configured time has expired.
Transmit only if the output changes: The output only transmits the current object
value if the object value has changed compared to the last transmission process.
After bus voltage return or an ETS programming operation, the output always trans-
mits.
Transmit cyclically: With this setting, the output transmits the current object value to
the KNX cyclically. After bus voltage return or after an ETS programming operation,
the cyclical transmission is only started once the first telegram has been received at
the input. If the ON / OFF delay is used, after bus voltage return or after an ETS pro-
gramming, operation cyclical transmission starts automatically once the delay time
has expired. The output also transmits as soon as a new telegram is received at the
input. At the same time, the cycle time for cyclical transmission is restarted!
Cycle time hours (0...99)
During cyclical transmission of the output, this parameter defines the cycle time.
Setting the cycle time hours.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
ON -> OFF / OFF -> OFF
ON -> --- / OFF -> OFF
ON -> ON / OFF -> ---
ON -> OFF / OFF -> ON
ON -> --- / OFF -> ON
ON -> OFF / OFF -> ---
always transmit when the input is updated
transmit only if the output changes
transmit cyclically