Objects For Forced Position; Command Value Status - Gira KNX 2139 00 Product Documentation

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Valve outputs | Command value status
Object polarity
The telegram polarity of the "Forced position - Activate / Deactivate" object is defined
here when the forced position object is enabled.
Status object
This parameter enables the "Forced position - Status" object.
Yes: The "Forced position - Status" object is visible. The polarity of the object
is defined: 1 = forced position active / 0 = no forced position
No : The "Forced position - Status" object is not visible.

9.7.2 Objects for forced position

Object no.
24, 39, 54,
69, 84, 99
1-bit input object for activating and deactivating of a forced position. The telegram
polarity can be configured.
Updates of the object from "Forced position active" to "Forced position active"
or from "Forced position inactive" to "Forced position inactive" produce no re-
action.
The status preset via the forced position object is stored internally in the
device after voltage failure and is restored automatically after voltage return.
Object no.
32, 47, 62,
77, 96, 107
1-bit output object for status message of a forced position. The polarity of the object
is defined: 1 = forced position active / 0 = no forced position

Command value status

9.8
Command value status
A status object can be optionally enabled for each valve output. The status object
makes the active command value of a valve output available either actively transmit-
ting or passively (object can be read out). In the status message, the actuator takes
all the functions into account which have an influence on the command value imple-
mented at the output. Depending on the configured data format of the input com-
mand value, the status object will possess the data formats named below...
Input command value "Switching (1-bit)":
Data format of status object "1-bit",
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Forced position -
Activate / Deactivate
Function
Forced position -
Status
1 = forced position active / 0 = no forced
position
0 = forced position active / 1 = no forced
position
Checkbox (yes / no)
Name
VO x - Input
Name
VO x - Output
Type
DPT
Flag
1-bit
1,003
C, -, W, -, U
Type
DPT
Flag
1-bit
1,003
C, R, -, T, A
Page 92 of 257