B0059001 / Rev. 2.3
Minimal wiring of interface
Operational condition: Setup - Edit
Condition!
1.
The unit must be in "Setup - Edit" condition.
2.
System parameter "Test job control mode: KM" (by SND40 key)
3.
Test job or speed measurement (is started by key operation and automatically terminated).
4.
The PLC must already have the tube prepared for rotation. The PLC must then accordingly output the signal "motor"
to rotate the tube.
Key / Start test job
Parallel Data Outputs
OUT2 / Ready for measuring
OUT5 / General fault
OUT7 / Motor
t1:
< 100 ms
t2:
The duration of the test procedure / speed measurement is depending on tube diameter and tube rotation rate.
t3:
≥ 0 ms
The duration of parameter optimization (test job / speed measurement) depends on tube diameter, tube rotation rate and
the time required for entering the parameters.
Test job:
Speed measurement
1)
Not mentioned inputs / outputs of the interface are not required for parameter programming.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Weld Seam Detection System R4000 SND40
for Tubes, Cans and Drums
1)
Transient time + 3 to 4 tube turns
approx. 60 s transient time + 5 tube turns
Manual
t3
t1
t2
Technical records
145