Weld seam detection system
Hide thumbs Also See for R4000:
Table of Contents

Advertisement

B0059001 / Rev. 2.3
Connection diagram
Connect the NT-NS-S according to the following scheme, use the stated cables.
This diagram is valid starting from serial number C1211)
Fig. 56: Connection diagram
Allocation of connections
Connection towards SND40 (HAN8)
Pin 1
+ 15 V
Pin 2
- 15 V
Pin 3
AGND
Pin 4
Measurement signal
Pin 5
Measurement signal
Pin 6
+ coil (ENABLE Power supply)
Pin 7
- coil (ENABLE Power supply)
Pin 8
Shield for sensor cable
Operation
For operating the power supply with the SND40 is necessary that at the SND40 pins 6 and 7 of the
HAN8 plug are wired. Furthermore, a magnetization of at least 29% must be set.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Weld Seam Detection System R4000 SND40
for Tubes, Cans and Drums
Note
For operating the power supply NT-NS-S, the cable breakage
monitoring must be switched off at the SND40.
Manual
Connection towards sensor (HAN8)
bridged
Pin 1
bridged
Pin 2
bridged
Pin 3
bridged
Pin 4
bridged
Pin 5
Pin 6
Pin 7
Pin 8
Technical data
+ 15 V
- 15 V
AGND
Measurement signal
Measurement signal
+ coil (60 V – 90 V DC)
- coil (60 V – 90 V DC)
NC