Table 24 Overview Of Parameterization Tools; Table 25 Parameterization Overview - WAGO 765-4102/0100-0000 User Manual

8-port-io-link master class b; profinet; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-4102/0100-0000
Tool
Control with PROFINET IO-Controller
WAGO Webserver I/O Field
WAGO I/O Field app
Three domains are distinguished for configuration and parameterization:
1. PROFINET configuration: PROFINET modules and submodules
2. Port configuration: digital input or output
3. IO-Link device configuration
The following table shows which tool can influence which domain.
Tool
PROFINET IO-Controller
WAGO Webserver I/O
Field
WAGO I/O Field app
WAGO IO-Link Configura-
tor
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Description
The PROFINET IO-Controller must be configured to
exchange process data with the 765 modules. The
GSDML file GSDML-Vx.xx-wago-series765-yyyym-
mdd.xml describes the WAGO I/O-System Field mod-
ule. The PROFINET IO-Controller configuration soft-
ware imports this GSDML file, and the user can config-
ure and parameterize one or more 765 modules. The
user loads the configuration onto the PROFINET con-
troller. The PROFINET controller configures and pa-
rameterizes the 765 module via PROFINET.
WAGO Webserver I/O Field is a Webserver that is in-
tegrated into the 765 module. Using a Web browser,
the user can display the Web pages and display and
modify parameters.
The WAGO I/O Field app is an app for mobile devices
that can communicate with a 765 module via Blue-
tooth
PROFINET Modules and
Port Configuration
Submodules
The PROFINET IO-Con-
The IO-Controller sets the
troller configures the
parameter the user selects
PROFINET modules and
on the basis of the param-
submodules of the 765
eters in the GSDML file.
module.
These parameters config-
ure each individual port
and determine whether the
port is used as a digital in-
put or digital output (or is
disabled).
Yes
Yes
Yes
Table 24: Overview of Parameterization Tools
®
.
Table 25: Parameterization Overview
IO-Link Device Configu-
ration
Input fields to read/write
index; expert knowledge;
the I/O Field Webserver
does not evaluate an
IODD;
Yes
IODD can be used by the
app to parameterize an IO-
Link device
Yes
IODD can be used by the
IO-Link configurator to pa-
rameterize an IO-Link de-
vice.
Functions
27

Advertisement

Table of Contents
loading

Table of Contents