765-4102/0100-0000
3. Configure the ports
4. Set the parameters
ð The parameters are imported from the GSDML file.
10.2.1.1.1 Selecting the Product
Select the product used from the device catalog.
Product: 765-4102
Name: 8PORT IOL-B FLD PN DC 24V 2.0A
10.2.1.1.2 Configuring the PROFINET Station Name and IP Address
When delivered and after a factory rest, the IO device has no PROFINET product name,
and the IP address is 0.0.0.0.
The IO-Device requires a unique PROFINET product name so the IO controller can com-
municate with the IO device.
Use the engineering software to assign the IO device a PROFINET product name.
The IO controller configures the IP address when PROFINET starts up.
10.2.1.1.3 Parameterizing Ports
Parameterize the ports using the information in section
figuration
10.2.1.1.4 Parameterizing the Submodule
Parameterize the submodule using the information in section
[} 41].
10.2.2 WAGO Webserver I/O Field
10.2.2.1 Opening WAGO Webserver I/O Field
This section describes how you can use the integrated software "WAGO Webserver I/O
Field" to get access to detailed information on the current operating state of the product
and make settings to affect the product's behavior.
ü Requirement: Opening the user interface of WAGO Webserver I/O Field requires that
product's IP address is configured and known.
•
Proceed as follows:
Enter the following text in the address bar of your Web browser to address the prod-
uct:
http://<IP-address-according-to-configuration>
e.g., http://192.168.10.2.
ð The Dashboard of WAGO Webserver I/O Field appears. You can now use the func-
tions described below.
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
[} 50].
Commissioning
8 Setting the PROFINET Con-
8 PROFINET Parameters
67