Functions
The measurements are performed for the module and for pin 1, pin 2 and pin 4 of each
port. The measured values can be displayed in the WAGO I/O Field Webserver or the
WAGO I/O Field app. Alternatively, an OPC UA client can read out the measured values
and display them.
In the module, the measured values are compared to limiting values. An alarm or event is
generated if a value falls above or below a limiting value (e.g., a temperature limiting
value). The module can send this alarm/event
• EtherCAT
diagnostic history object (Index 0x10F3),
• to the OPC UA client upon: OPC UA: event.
The OPC UA client application can use the measured values, for example to implement
load management. You can find information on load management in
Supply
5.4 Overload protection
The module has built-in overload protection and periodically measures the current, volt-
age and temperature.
If the output current, supply voltage or temperature exceeds the maximum value, the
module switches off a pin/port
5.5 Parameterization Tools
5.5.1 Overview
There are several ways to set the module's parameters. The following table provides an
overview of the tools.
Tool
Controller with EtherCAT
master
WAGO I/O Field Webserver The WAGO I/O Field Webserver is a Webserver that is integrated into the 765
WAGO App I/O Field
WAGO IO-Link Configurator WAGO IO-Link Configurator is software for configuring the WAGO IO-Link mas-
A distinction is made between two parts of the configuration and parameterization:
1. EtherCAT configuration: select EtherCAT
28
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
®
: Send emergency telegram to the controller, or the controller can read the
[} 34].
Description
®
The EtherCAT master must be configured to exchange process data with the
765 Series modules.
The WAGO_series765.xml and WAGO_series765_diag.xml device descrip-
tion files contain the WAGO I/O System Field modules. The configuration soft-
ware of the EtherCAT
and parameterize one or more 765 Series modules.
The user loads the configuration onto the EtherCAT
master configures and parameterizes the 765 modules via EtherCAT
Series module. With a Web browser, users can view the Web pages and display
and modify parameters.
The WAGO I/O Field app is an app for mobile devices that can communicate
with a 765 Series module via Bluetooth
the 765 Series module, read and write process data and display diagnostics.
ters and the IO-Link devices.
Table 26: Overview of Parameterization Tools
®
master imports these XML files, and the user can select
®
®
. With the app, the user can parameterize
®
module
765-1205/100-000
8 Design Power
®
master. The EtherCAT
®
.