765-4102/0100-0000
The Backup Level parameter determines the system behavior when a device connected
to the port is replaced with respect to continued operation with unmodified device param-
eters.
This parameter can have three different values:
Backup Level
Commissioning ("Disable")
Production ("Backup/Restore")
Production ("Restore")
The Validation and Backup drop-down list offers the following options for setting the In-
spection Level and Backup Level parameters:
Table 51: Setting the Inspection Levels and Backup Levels for Device Check during Validation and Backup
Selection Option
No device check
Type compatible device
(V1.0)
Type compatible device
(V1.1)
Type compatible device
(V1.1) with backup + re-
store
Type compatible device
(V1.1) with restore
VendorID Input Field
This element contains the expected manufacturer ID (VendorID, 2 bytes) of the con-
nected device. The permissible values range from 1 to 0xFFFF. This information is re-
quired for the device check for type compatibility. It can be omitted if [No device check]
is selected.
DeviceID Input Field
This element contains the expected device ID (DeviceID, 3 bytes) of the connected de-
vice. The permissible values range from 1 to 0xFFFFFF. This information is required for
the device check for type compatibility. It can be omitted if [No device] is selected.
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Table 50: Possible Values of the Backup Level Parameter
Meaning
Parameter data of the old device is not saved for trans-
fer to the new device. Therefore, if the device is re-
placed, the new device must be parameterized anew.
Changes to all active parameters within the device are
copied and saved. Thus all parameter data of the old
device is stored for transfer to a new device.
Device replacement with automatic or semi-automatic
data storage is supported.
Changes to all active parameters within the device are
not copied and saved. Only special parameter data of
the old device is stored for transfer to a new device.
Device replacement with automatic or semi-automatic
data storage is only supported for these "frozen" pa-
rameters.
Inspection Level
Backup Level
NO_CHECK
Disable
TYPE_COMP
Disable
TYPE_COMP
Disable
TYPE_COMP
Backup + Restore
TYPE_COMP
Restore
Commissioning
Explanation
No device check is per-
formed.
Device check for type-
compatible device per IO-
Link specification 1.0
Device check for type-
compatible device per IO-
Link specification 1.1
Device check for type-
compatible device per IO-
Link specification 1.1 with
backup & restore function-
ality
Device check for type-
compatible device per IO-
Link specification 1.1 with
restore functionality
81