WAGO 765-4102/0100-0000 User Manual page 79

8-port-io-link master class b; profinet; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-4102/0100-0000
Name
VendorID
DeviceID
Changes to settings require operator or admin rights. If you do not have these, the Con-
figuration tab is grayed out, and the displayed values cannot be edited.
If cyclic data exchange takes place via PROFINET, no configuration is possible. In this
case, a message appears:
Note: Changing configuration not allowed because interface state
is "communicating."
To makes changes to a port's configuration:
1. Select the desired port (port X01, port X02 etc.) from the menu
2. Open the Configuration tab
3. Configure pin 4 by setting the port operating mode
4. If applicable, configure the filter time for the signals of the digital inputs
5. If applicable, configure the device check for validation and backup
6. If applicable, configure pin 2 by setting the I/Q behavior
7. If applicable, enter the expected vendor ID
8. If applicable, enter the expected device ID
9. If applicable, set the expected cycle time
10. Click the [Apply] button
ð Your changes now take effect.
Configuring the Operating Mode for Pin 4 of the Port
You can select the port operating mode for pin 4 of the selected IO-Link port from the
Port mode drop-down list. The following operating modes are available:
Table 47: "Port Mode" Drop-Down Menu: Selecting the Operating Mode for Pin 4 of the Selected IO-Link Port
Selection Option
Deactivated
IOL Manual
IOL Autostart
Digital input, normally open
Digital input, normally closed
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Table 46: Port Configuration Settings for IO-Link Devices
Type
Input field
Input field
Explanation
The port is disabled. L+ is switched off. The process
data (both input and output) is set to 0. The master no
longer performs actions related to this port.
The port is used as an IO-Link port with manual (user-
defined) configuration. Vendor ID, Device ID and Revi-
sion ID are validated.
The port is used as an IO-Link port with automatic
start. No configuration or device validation occurs.
The port is operated as a digital input (pin 4 serves a
data line). All elements of the port configuration are ig-
nored except for the input and output data length.
The port is operated as a digital input (pin 4 is config-
ured as an input). The signal on the pin is not inverted.
All elements of the port configuration are ignored ex-
cept for the input and output data length.
Commissioning
Explanation
Expected manufacturer ID of the at-
tached module
Expected device ID of the attached
module
79