WAGO 765-4102/0100-0000 User Manual page 133

8-port-io-link master class b; profinet; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-4102/0100-0000
Channel Error
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
0x9502
Process Alarms
A process alarm is triggered by an IO-Link device. An IO-Link device sends the "Event
Code" and the "Event Qualifier" of the event to the IO-Link master. The following values
are set in the event qualifier:
TYPE = 1 (Notification)
MODE = 1 (Single shot)
SOURCE = 0 (Device/remote)
The IO-Link master sends this event to the IO controller as a process alarm. The value of
"Channel Error" is 0x9500 for standard events and 0x9501 for manufacturer-specific
events. The IODD of the IO-Link device contains manufacturer-specific events with mes-
sage text.
The following table describes the possible standard events of the IO-Link device.
Channel Error
(PROFINET)
0x9500
0x9500
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Extended Chan-
Description
nel Error Type
0x1802
Incorrect device identification
0x1803
Incorrect device identification
0x1804
Short circuit on C/Q
0x1805
PHY overtemperature
0x1806
Short circuit on L+
0x1807
Overcurrent on L+
0x1808
Device event overflow
0x1809
Backup inconsistency
0x180A
Backup inconsistency
0x180B
Backup inconsistency
0x180C
Backup inconsistency
0x180D
Parameter inconsistency
0x180E
P24 (class B) missing or has under-
voltage
0x180F
Short circuit on P24 (class B)
0x1810
Short circuit on I/Q
0x1811
Short circuit on C/Q
0x1812
Overcurrent on I/Q
0x6000
Invalid cycle time
0x6001
Revision error (incompatible proto-
col version)
0x6002
ISDU batch failed
Extended
Description of the Error Function
Channel Error
on the Connected IO-Link Device
Type
(PROFINET)
0x1000
General malfunction
0x4000
Temperature error
Table 85: IO-Link Master Diagnostic Alarms
Corrective Action
Check port configuration parame-
ters
Check port configuration parame-
ters
Check wiring
Check temperature and load
Check wiring
Check power supply (e.g., 1L+)
Contact device manufacturer
Access outside the memory area
(2048 octets)
Eliminate identity error
Unspecified error during data stor-
age
Eliminate upload error
Eliminate download error
Check power supply
Check wiring (e.g., 2L+)
Check wiring
Check wiring
Check load
Check port configuration parame-
ters
Check port configuration parame-
ters
Fix parameter inconsistency
Table 86: Process Alarms for IO-Link Device Diagnostics
Corrective Action on the Con-
nected
IO-Link Device
IO-Link device reports unknown error
Eliminate overload
Diagnostics
133