Power Supply; Electrical Safety; Environmental Conditions; Table 10 Power Supply - WAGO 765-4102/0100-0000 User Manual

8-port-io-link master class b; profinet; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-4102/0100-0000
Circuit
Self-protection
Voltage drop through high-side path
Maximum capacitive load
Maximum inductive load
Diagnostics (1L+, 2L+)

4.4.4 Power Supply

Voltage 1L, 2L
Undervoltage warning
Overvoltage warning
Module power consumption
Power consumption of supply connections
Conductor cross-section
Reverse voltage protection

4.4.5 Electrical Safety

Insulation resistance
Test voltage
Min. creepage distance
Requirements
• Use of PELV/SELV power supplies with fault voltage limited to 60 VDC.
• When SELV power supplies are used: SELV power supplies with supply via the same
network phase
• If PELV (Protective Extra Low Voltage) power supplies are used: PELV (Protective Ex-
tra Low Voltage) power supplies with a secondary power supply connection to the
common reference point

4.4.6 Environmental Conditions

Surrounding air temperature (operation)
Surrounding air temperature (storage)
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
High-side driver; no reverse current protection of the
1L+/2L+ output
Overcurrent, overload and overtemperature
Less than 200 mV
1000 μF parallel to 24 Ω; 0.1 Hz
470 μF parallel to 12 Ω; 0.1 Hz
220 μF parallel to 6 Ω; 0.1 Hz
1.15 H / 2 A; 0.2 Hz; DC13
Events: overcurrent, overload and overtemperature
24 VDC, –25 %/+30 % (18 VDC ...31.2 VDC)
Voltages above 34 V can permanently damage the
product.
Voltages below approx. 10 V lead to a product reset.
17.0 V (17.5 V −3 %) ON message,
18 V (17.5 V +3 %) OFF message
32.1 V (31.2 V +3 %) ON message,
30.3 V (31.2 V −3 %) OFF message
1L: 0.2 A (at 24 VDC)
2L: 0.1 A (at 24 VDC)
Max. 16 A; ensure external limitation or use fuses in
the cables
The maximum total current of the device, including
transmission between the power supply connections,
must not exceed 16 A for both 1L and 2L individually. If
additional modules are connected to X32 (PWR OUT),
it may be necessary for the maximum total current to
be monitored with external power supply management.
Maximum current: Observe derating as a function of
temperature
2
For UL-compliant use: 2.5 mm
Yes
60 VDC
550 VAC RMS
0.7 mm
–25 °C ... +70 °C
–40 °C ... +80 °C
Properties
19