Properties
Maximum temperature change
Relative humidity (operation)
Pollution degree
Operating altitude
Overvoltage category
Protection type
Protection class

4.4.7 Communication

Communication Interfaces
Protocols
PROFINET IO-Device
Input data
Output data
Alarm types
Identification & Maintenance (I&M)
Topology recognition
Minimum cycle time (MinDeviceInterval)
PROFINET IO specification
Conformance Class
Data transport layer
Interface type
Autonegotiation, autocrossover
OPC UA Server
OPC UA Server
Server profile
Protocol
User access
Number of sessions
20
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
3 K / min
5 % ... 95 %
3 (EN 60664-1)
0 ... 2000 m
II (EN 60664-1)
IP67 (EN 60529)
III (EN 61140)
ETHERNET, IO-Link, Bluetooth
PROFINET, HTTP, OPC UA, IO-Link
16 ... 288 bytes
Operation with 8 IO-Link 32 I / 32 O + PQI: 288 bytes
(= 266 bytes of process data + 13 bytes of IOPS + 9
bytes of IOCS)
Operation with 16 DIs: 24 bytes (= 10 bytes of process
data + 13 bytes of IOPS + 1 byte of IOCS)
Operation with 16 DOs: 16 bytes (= 2 bytes process
data + 5 bytes IOPS + 9 bytes IOCS)
16 ... 280 bytes
Operation with 8 IO-Link 32 I / 32 O + PQI: 280 bytes
(= 258 bytes of process data + 9 bytes of IOPS + 13
bytes of IOCS)
Operation with 16 DIs: 16 bytes (= 2 bytes of process
data + 1 bytes of IOPS + 13 byte of IOCS)
Operation with 16 DOs: 24 bytes (= 10 bytes process
data + 9 bytes IOPS + 5 bytes IOCS)
Diagnostic alarm, process alarm, plug/pull alarm
I&M0-4
LLDP, SNMP V1, Physical Device Record Objects
RT_CLASS_1: 1 ms (min. SendClockFactor 32)
RT_CLASS_3: 1 ms (min. SendClockFactor 32)
V2.3
"Legacy Startup" of specification V2.2 is supported
C
ETHERNET II, IEEE 802.3
100BASE-TX, potential-free
Yes
Diagnostic functions added in accordance with "IO-
Link Companion Specification"
Micro Embedded Device
OPC UA TCP
Anonymous (read access only)
Username/password (read and write access)
2