Parameter Group
IO-Link port parame-
ters (continued)
IO-Link port parame-
ters (continued)
The "Port cycle time" parameter contains a factor (bits 0 to 5) and a time basis (bits 6+7).
The following table describes how the port cycle time is calculated from the factor and the
time basis.
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Table 33: Parameters of the "IO-Link XX I / XX O + PQI" Submodule
Parameters
Default
Validation/backup
0
I/Q behavior
1
Port cycle time
-
Vendor ID
-
Device ID
-
Value Range
Description
0: no device check
No product check oc-
curs for validation or
backup of connected
IO-Link slave prod-
ucts
1: type-compatible
A product check for
device (V1.0)
the indicated device
type is performed for
2: type-compatible
validation or backup
device (V1.1)
of connected IO-Link
3: type-compatible
slave products
V1.1 device with
backup + restore
4: type-compatible
V1.1 device with re-
store
0: not supported
Pin 2 is not used
1: digital input
Pin 2 is a digital input
2: digital output
Pin 2 is a digital out-
put
5: static on
High signal on pin 2
0, 4 ... 191
Port cycle time
0: calculated by IO-
Link master
4 ... 191: see section
8 PROFINET Pa-
rameters [} 45]
0 ... 65535
Manufacturer ID
The manufacturer ID
is used to check
whether an IO-Link
device from the right
manufacturer is con-
nected. For the value
of the manufacturer
ID, see the docu-
mentation of the sen-
sor/actuator used.
0 ... 4294967295
Device ID
The device ID is
checked to see
whether the right IO-
Link device is con-
nected. For the value
of the device ID, see
the documentation of
the sensor/actuator
used.