Table 21 Process Data, Io-Link Port Submodule (Do); Table 22 Port Qualifier Information; Table 23 Provider And Consumer Status - WAGO 765-4102/0100-0000 User Manual

8-port-io-link master class b; profinet; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

Functions
Byte Offset
x
PQI (Port Qualifier Information)
The PQI (Port Qualifier Information) provides status information for the IO-Link port IO-
Link device.
Bit
0
1
2
3
4
5
6
7
Provider and Consumer Status
Bits
0 ... 4
24
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Table 21: Process Data, IO-Link Port Submodule (DO)
Bit
Input Process Data
(PD_IN)
0
0
1 ... 7
0
Flag
-
-
NewPar
SubstDev
PortActive
DevCom
DevErr
PQ
Name
-
765-4102/0100-0000
Output Process Data
(PD_OUT)
Port X01, DO (pin 4) or
port X02, DO (pin 4) or
...
port X08, DO (pin 4)
0
Table 22: Port Qualifier Information
Description
Reserved, 0
Reserved, 0
New parameters
0: No IO-Link device product param-
eter update detected
1: IO-Link device product parameter
update detected: IO-Link master
performs a "data storage upload,"
and a new IO-Link device backup
object (0xB904) is available
Substitute product detected
0: No substitute product detected
(identical serial number)
1: Substitute product detected (dif-
ferent serial number)
Port activation
0: Port was disabled via port func-
tion
1: Port is enabled (default)
IO-Link device communication
0: No IO-Link device present
1: IO-Link device detected in state
PREOPERATE or OPERATE
Port/device error
0: No error/warning occurred
1: Error/warning occurred on port or
IO-Link device
Validity of the device process data
0: Invalid I/O process data from IO-
Link device
1: Valid I/O process data from IO-
Link device
Table 23: Provider and Consumer Status
Description
Reserved, always 0