The serial number is also checked. This ensures that IO-Link devices can only be re-
placed by authorized personnel. To allow this, it is necessary to revert the inspection level
to at least "compatible," enter the new serial number and then reset the inspection level to
"identical."
Data Storage / Data Storage Mode
This function is only available for IO-Link devices of IO-Link versions V1.1 and higher.
You can select from the following operating modes:
• Disabled
No parameter server function
• Auto
Changes to the parameterization in the device are automatically applied to the parame-
ter server
• Download
The data in the parameter server (master) takes precedence. If a device is replaced, its
parameters are set from the parameter server.
This setting is selected if an application is "withdrawn" and modification needs to be
prohibited. In this mode, no changes can be made with the tool. They are overwritten
immediately by the data storage mechanism.
• Upload
The data in the device takes precedence and is applied to the parameter server. This
setting can be used if the devices are pre-parameterized and the data is to be applied
to the master. Furthermore, this also allows a master to be replaced if all devices have
already been parameterized and their data is to be applied to the master.
Data Storage Commands
The parameterization can also be exchanged manually between the data storage and IO-
Link device. The following commands are available: Clear, Upload and Download.
Process Data Configuration
Here you can view/modify the process data width setting for the PLC. "Configured
Length" indicates the process data width for the PLC. "Device Length" indicates the num-
ber of input or output bytes of the IO-Link device. A color change indicates that too little of
the process image is configured for the PLC.

10.2.3.3.8 IO-Link Master Control 2

This control is used for all newly integrated IO-Link masters, especially if they are modu-
lar or require special settings beyond the normal port configuration.
For the new control, the information is divided into three tabs:
• Common
Identification data from the master device description (IOLM)
Identification data of the specific master
108
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
765-4102/0100-0000