The top third of the IO-Link master control contains information on the WAGO IO-Link
master (identification section). The table in the middle shows all the available IO-Link
ports and their configuration. Below that there are buttons for searching for connected IO-
Link devices and transferring the WAGO IO-Link master's data storage data.
The lower section shows detailed information on the port selected in the table.
10.2.3.3.7.1 Searching for IO-Link Masters
There are several options for searching for IO-Link masters and incorporating them into
the project. With integrated execution via TCI, these functions are disabled, since the
configuration is performed with the PLC engineering software.
In the topology:
Right-click in an empty area
ð A search is performed for all IO-Link masters.
Right-click on fieldbus or ETHERNET icon
ð A search is performed for only IO-Link masters with the corresponding communica-
tion interface.
[Search Masters] button:
If the master was selected from the device catalog and added to the topology, you can
search for the exact configured IO-Link master with this button.
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Figure 32: IO-Link Master Control General Settings
Commissioning