Diagnostic Alarms
Diagnostic alarms originate from the IO-Link master. They indicate events on the IO-Link
master or its ports. The following values are set in the "Event Qualifier":
TYPE = 2 (Warning) or 3 (Error)
MODE = 2 (Event disappears) or 3 (Event appears)
SOURCE = 1 (Master/local)
The IO-Link master sends this event to the IO controller as a diagnostic alarm. The value
of "Channel Error (PROFINET)" is 0x9502.
The following table lists the numbers of the IO-Link master diagnostic alarms.
Channel Error
0x9502
0x9502
0x9502
132
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Alarm
Description
Overvoltage, 1L
Overvoltage in supply cable 1L
The supply cable has exceeded the limiting
value for the maximum voltage
Overtemperature
Overtemperature
The device temperature has exceeded the
upper limiting value
Overload, 1L
Overload in supply cable 1L
The total current in supply cable 1L has ex-
ceeded the upper limiting value
Overload, 2L
Overload in supply cable 2L
The total current in supply cable 1L has ex-
ceeded the upper limiting value
Undertemperature
Undertemperature
The device temperature has fallen below
the lower limiting value
Undervoltage, 2L
Undervoltage in supply cable 2L
The power supply for supply cable 2L has
fallen below the limiting value for the mini-
mum voltage
Overvoltage, 2L
Overvoltage in supply cable 2L
The power supply for supply cable 2L has
exceeded the limiting value for the maxi-
mum voltage
Forcing operating mode
Forcing operating mode active (activated
active
by Web client or OPC UA client)
Short circuit on pin 4
Short circuit detected on pin 4
Short circuit on pin 2
Short circuit detected on pin 2
Short circuit on pin 1
Short circuit detected on pin 1
Extended Chan-
Description
nel Error Type
0x17FF
Process data error
0x1800
No device access / loss of commu-
nication
0x1801
Start parameter error
765-4102/0100-0000
Table 84: General Alarms
Corrective Action
Check supply voltage
Eliminate external heat
source or overload
Eliminate overload
Eliminate overload
Thermally insulate the de-
vice
Check supply voltage
Check supply voltage
The Web client or OPC UA
client should exit forcing op-
erating mode as soon as
forcing is no longer needed
Eliminate short circuit
Eliminate short circuit
Eliminate short circuit
Table 85: IO-Link Master Diagnostic Alarms
Corrective Action
Check submodule configuration
Check IO-Link port
Check parameters