6.3.2 Setting the PROFINET Configuration

For each IO-Link port, specify the type of IO-Link device that is connected to the port: dig-
ital input, digital output or IO-Link device.
The PROFINET IO-Link product has a modular structure. Slot 0 is the PROFINET access
point with four submodules. Slot 1 contains the IO-Link master and eight IO-Link ports.
Slot
0
0
0
0
1
1
1
1
1
1
1
1
1
Submodule
Digital input
Digital output
IO-Link 32 I / 32 O + PQI
IO-Link 16 I / 16 O + PQI
IO-Link 4 I / 4 O + PQI
IO-Link 2 I / 2 O + PQI
IO-Link 1 I / 1 O + PQI
IO-Link 32 I + PQI
50
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Subslot
Submodule
1
DAP
32768
PN-IO
32769
Port 1
32770
Port 2
1
IO-Link master
2
Port X01 configuration
3
Port X02 configuration
4
Port X03 configuration
5
Port X04 configuration
6
Port X05 configuration
7
Port X06 configuration
8
Port X07 configuration
9
Port X08 configuration
Description
Input
Process Data (PD_IN)
Digital input
1 byte
Digital output
-
IO-Link with 32 bytes of in-
32 bytes + 1 byte PQI
put data and 32 bytes of
output data and Port Qual-
ifier Information
IO-Link with 16 bytes of in-
16 bytes + 1 byte PQI
put data and 16 bytes of
output data and Port Qual-
ifier Information
IO-Link with 4 bytes of in-
4 bytes + 1 byte PQI
put data and 4 bytes of
output data and Port Qual-
ifier Information
IO-Link with 2 bytes of in-
2 bytes + 1 byte PQI
put data and 2 bytes of
output data and Port Qual-
ifier Information
IO-Link with 1 byte of input
1 byte + 1 byte PQI
data and 1 byte of output
data and Port Qualifier In-
formation
IO-Link with 32 bytes of in-
32 bytes + 1 byte PQI
put data and Port Qualifier
Information
765-4102/0100-0000
Table 37: PROFINET Modules and Submodules
Description
Product access point
(fixed)
PROFINET interface
(fixed)
Port 1 (fixed)
Port 2 (fixed)
IO-Link master (fixed)
2 input bytes and 2 output
bytes
Configures the port: digital
input, digital output or IO-
Link communication; for
selection, see the following
table
Table 38: Port Submodules
Output
Process Data (PD_OUT)
-
1 byte
32 bytes
16 bytes
4 bytes
2 bytes
1 byte
-

Advertisement