11.2.1.10 Events Triggered by the IO-Link Master

Events on the IO-Link master or its ports are reported by the IO-Link master to the Ether-
CAT slave, which forwards this to the EtherCAT master in the form of diagnostics.
The following values are set in the event qualifier:
TYPE = 2 (Warning) or 3 (Error)
MODE = 2 (Event disappears) or 3 (Event appears)
SOURCE = 1 (Master/local)
The following table lists the IO-Link event codes associated with IO-Link master events
and provides information on how to remedy faults.
IO-Link Event Code Description
0x17FF
0x1800
0x1801
0x1802
0x1803
0x1804
0x1805
0x1806
0x1807
0x1808
0x1809
88
Product manual | Version: 1.0.0
8DIO FLD EC DC 24V 2.0A
Alarm
Description
The total current in supply line 1L has ex-
ceeded the upper limiting value.
Undertempera-
Undertemperature
ture
The device temperature has fallen below
the lower limiting value.
Undervoltage,
Undervoltage in supply line 2L
2L
The power supply for supply line 2L has
fallen below the limiting value for the mini-
mum voltage.
Overvoltage,
Overvoltage in supply line 2L
2L
The power supply for supply line 2L has ex-
ceeded the limiting value for the maximum
voltage.
Forcing operat-
Forcing operating mode active (activated by
ing mode active
Web client or OPC UA client)
Short circuit on
Short circuit detected on pin 4
pin 4
Short circuit on
Short circuit detected on pin 2
pin 2
Short circuit on
Short circuit detected on pin 1.
pin 1
Process data error
No device access / loss of communi-
cation
Start parameter error
Incorrect device identification
Incorrect device identification
Short circuit on C/Q
PHY overtemperature
Short circuit on L+
Overcurrent on L+
Device event overflow
Backup inconsistency
765-1205/0100-0000
Remedy
Thermally insulate the device
Check supply voltage
Check supply voltage
The Web client or OPC UA
client should exit the Forcing op-
erating mode as soon as forcing
is no longer needed.
Eliminate short circuit.
Eliminate short circuit.
Eliminate short circuit.
Table 70: IO-Link Master Events
Remedy
Check submodule configuration
Check IO-Link port
Check parameters
Check port configuration parameters
Check port configuration parameters
Check wiring
Check temperature and load
Check wiring
Check power supply (e.g., 1L+)
Contact device manufacturer
Access outside the memory area (2048 octets)