11.2.1.10 Events Triggered by the IO-Link Master

Events on the IO-Link master or its ports are reported by the IO-Link master to the Ether-
CAT® slave, which forwards this to the EtherCAT® master in the form of diagnostics.
The following values are set in the event qualifier:
TYPE = 2 (Warning) or 3 (Error)
MODE = 2 (Event disappears) or 3 (Event appears)
SOURCE = 1 (Master/local)
The following table lists the IO-Link event codes associated with IO-Link master events
and provides information on how to remedy faults.
IO-Link Event Code Description
0x17FF
0x1800
0x1801
0x1802
0x1803
0x1804
0x1805
0x1806
0x1807
0x1808
0x1809
0x180A
0x180B
0x180C
0x180D
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
Alarm
Description
Undervoltage,
Undervoltage in supply line 2L
2L
The power supply for supply line 2L has
fallen below the limiting value for the mini-
mum voltage.
Overvoltage,
Overvoltage in supply line 2L
2L
The power supply for supply line 2L has ex-
ceeded the limiting value for the maximum
voltage.
Forcing operat-
Forcing operating mode active (activated by
ing mode active
Web client or OPC UA client)
Short circuit on
Short circuit detected on pin 4
pin 4
Short circuit on
Short circuit detected on pin 2
pin 2
Short circuit on
Short circuit detected on pin 1.
pin 1
Process data error
No device access / loss of communi-
cation
Start parameter error
Incorrect device identification
Incorrect device identification
Short circuit on C/Q
PHY overtemperature
Short circuit on L+
Overcurrent on L+
Device event overflow
Backup inconsistency
Backup inconsistency
Backup inconsistency
Backup inconsistency
Parameter inconsistency
Remedy
Check supply voltage
Check supply voltage
The Web client or OPC UA
client should exit the Forcing op-
erating mode as soon as forcing
is no longer needed.
Eliminate short circuit.
Eliminate short circuit.
Eliminate short circuit.
Table 78: IO-Link Master Events
Remedy
Check submodule configuration
Check IO-Link port
Check parameters
Check port configuration parameters
Check port configuration parameters
Check wiring
Check temperature and load
Check wiring
Check power supply (e.g., 1L+)
Contact device manufacturer
Access outside the memory area (2048 octets)
Fix identity error
Unspecified error during data storage
Fix upload error
Fix download error
Diagnostics
109