KEB COMBIVERT F5 BASIC Applications Manual page 209

Hide thumbs Also See for COMBIVERT F5 BASIC:
Table of Contents

Advertisement

Parameter Sets
Input-coded set selection
Fig. 6.8.7.c Input-coded parameter set selection (Fr.2=3)
ID IB
I4
I2
I1
Fr.2 =
0
0
0
0
0
0
0
0
0
1
0
0
0
2
0
0
0
3
0
0
0
4
0
0
0
5
0
0
0
0
5
0
3
0
0
5
0
3
0
1
Reset set input selection (Fr.11)
©
KEB Antriebstechnik,2002
All rights reserved
With input-coded set selection
-
maximally 7 of the internal or external inputs may be programmed to set selection
(0...7 sets) to avoid set selection errors.
-
the lowest of the selected inputs has priority at Fr.2 = „3"
(ST>RST>R>F>I1>I2>I3>I4>IA>IB>IC>ID)
-
the highest of the selected inputs has priority at Fr.2 = „4"
(ID>IC>IB>IA>I4>I3>I2>I1>R>F>RST>ST)
Example1: With 5 inputs (I1, I2, I4, IB and ID) set 0...5 shall be selected.
1.)
Adjust parameter Fr. 7 to value „2736"
2.)
Adjust Fr.2 to value „3" (set selection input-coded via terminal strip)
ID
Set Set
3
4
0
0
IB
1
1
2
2
I4
3
3
4
4
I2
5
5
3
5
1
5
I1
Set
5
4
Set
3
Set
2
Set
1
Set
0
Set
This parameter defines an input, with which one can switch independently of the
current parameter set in to parameter set 0 (see table at Fr.7). This function is only
activ at Fr.2 = 0...4.
with static input assignment the inverter remains in set 0 as long as the input is
set.
with edge-triggered inputs set 0 is always activated with the 1st edge. With the
2nd edge the set activated by the other inputs is selected again.
Name: Basis
KEB COMBIVERT F5
Functional Description
Date
17.04.02
Chapter
Section
Page
7
6
8
7
6