KEB COMBIVERT F5 BASIC Applications Manual page 53

Hide thumbs Also See for COMBIVERT F5 BASIC:
Table of Contents

Advertisement

CP - Parameter
Intermediate circuit voltage/
Peak value
Output voltage
4.3.5 Basic Adjustment
of the Drive
Minimum frequency
Maximum frequency
©
KEB Antriebstechnik, 2001
All Rights reserved
CP.8 makes it possible to recognize short-time voltage rises within an operating cycle.
For that the highest value of CP.7 is stored in CP.8. The peak value memory can be
cleared by pressing the UP, DOWN or ENTER key or over bus by writing any value
you like to the address of CP.8. The switch off of the inverter also clears the memory.
Display of the actual output voltage in volt.
The following parameters determine the fundamental operating data of the drive. They
should be checked and/or adapted to the application.
With this frequency the inverter operates without presetting an analog set value.
Internal limiting of the fixed frequencies CP.19...CP.21.
Adjustment range:
Resolution:
Factory setting:
With this frequency the inverter operates with maximum analog set value.
Internal limiting of the fixed frequencies CP.19...CP.21.
Adjustment range:
Resolution:
Factory setting:
Name: Basis
KEB COMBIVERT F5-G / B
Operation
f
0...400 Hz
CP.11
0,0125 Hz
0,0 Hz
CP.10
0V
0...400 Hz
0,0125 Hz
70 Hz
Date
Chapter
4
04.12.01
4
U
REF
10V
Section
Page
7
3
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combivert f5 generalCombivert f5 servoCombivert f5 multi

Table of Contents