Operating and Appliance Data
ru.17
Active current
Adr.
0211h
Display of the torque-forming active current (stator losses already deducted). Negative current corresponds to generatoric
operation, positive current corresponds to motoric operation. The more precise the motor data are entered, the more
precise is the indication of the active current. The maximum values depend on the size of the inverter.
ru.18
DC-link voltage
Adr.
0212h
Display of current DC-link voltage. Typical values are
Normal operation: 230V-class 300-330V
400V-class 530-620V
ru.19
DC-link voltage / peak value
Adr.
0213h
ru.19 permits the detection of short-time voltage rises within an operating cycle. The higest occurred value of ru.18 is
stored in ru.19. The peak value memory can be cleared by pressing the keys UP, DOWN or ENTER and by bus through
writing any chosen value to the address of ru.19. Switching off the inverter also results in a clearing of the memory.
ru.20
Output voltage
Adr.
0214h
Display of the current output voltage.
©
KEB Antriebstechnik, 2002
All rights reserved
min
-unit-depend.
+unit-dependent
min
0
1000
over volt. (E.OP): approx. 400V
min
max
0
1000
min
0
778
Name: Basis
KEB COMBIVERT F5-G / B
Functional Description
max
0.1
max
1
approx. 800V
1
max
1
default
A
-
default
V
-
under volt. (E.UP): approx. 216V
approx. 240V
default
V
-
default
V
-
Date
Chapter
Section
6
1
24.06.02
6
Page
9

Hide quick links: