Special Functions
6.9.2
Energy Saving
Function
(only F5-B, F5-G and
F5-M if cS.0=0)
Used Parameters
R/W
PROG.
Param.
Adr.
uF.6
0506h
uF.7
0507h
uF.8
0508h
©
KEB Antriebstechnik, 2002
All rights reserved
The energy saving function allows the lowering or raising of the current output voltage.
In accordance with the activation conditions defined in uF.6, the voltage valid according
to the V/Hz-characteristic is changed in percent onto the energy saving level (uF.7).
However, the maximal output voltage cannot be higher than the input voltage even if
the value is > 100 %. The function is used for example in cyclic executed load/no-load
applications. During the no-load phase the speed is maintained, but energy is saved
as a result of the voltage reduction.
uF.8
Input selection
Energy saving function
0...4095 (default 0)
also see 6.3
„Digital inputs"
ENTER
min
-
0
-
0.0 %
130.0 %
-
0
4095
Name: Basis
KEB COMBIVERT F5
Functional Description
uF.7
Energy saving factor
0.0...130.0 % (default 70 %)
uF.6
Energy saving function / Activation
0
Function off
1
Generally on
2
When actual = setpoint frequency/speed
3
Activation through programmable inputs
4
Generally at rotation direction forward
5
Generally at rotation direction reverse
6
Rotation direction forward and actual = set freq./speed
7
Rotation direction reverse and actual = set freq./speed
f
; n
act
act
f
/n
set
set
uF.7
Example: uF.6 = 2, uF.7 = 50 %
Step
max
default
7
1
0
1 %
70 %
1
128
; U
Hysteresis
A
-
-
-
Date
Chapter
Section
6
18.04.02
6
t
Page
9
5