Digital In- and Outputs

6.3.19 Inverting of Flags

(do.25...do.32)

6.3.20 Selection of Flags

(do.33...do.40)

6.3.21 Linking the Flags

(do.41)
Fig. 6.3.19 Linking the switching conditions in logic step 2
do.41
8
do.33
&
1 Bit 0
> 1
0
8
do.34
&
1 Bit 1
> 1
0
8
do.40
&
1 Bit 7
> 1
0
©
KEB Antriebstechnik, 2002
All rights reserved
Fig. 6.3.18 Inversion and selection of switching conditions from step 1
Bit 0
Bit 1
Bit 2
Bit 3
do.24
Bit 4
Bit 5
Bit 6
Bit 7
With the parameters do.25...do.32 each of the 8 flags (bit 0...7) from logic step 1
can be inverted separately. Through this function it is possible to set any chosen
flag as Non-flag. The parameter is bit-coded. According to Fig. 6.3.18 the weighting
of the switching conditions to be inverted must be entered in do.25...do.32. If several
flags shall be inverted, the sum is to be formed.
In the second logic step a selection of the flags of the first logic step can be made.
The selection is done for each output separately, where one can choose between
no one and up to all 8 flags. According to Fig. 6.3.18 the weighting of the selected
flags is to be entered into do.33...do.40. If several flags shall be selected, the sum
is to be formed.
After the switching conditions are selected for each output, it can now be determined,
how these are linked. As a default all conditions are OR-operated, i.e. if one of the
selected conditions is met, the output switches. Another possibility is the AND-
operation, which is adjusted with do.41. AND-operation means, that all selected
condtions must be fulfilled before the output switches.
Parameter do.41 is bit-coded. The table under 6.3.20 shows the assignment.
Terminal
Name
O1
X2A.18
X2A.19
X2A.24...26
O2
X2A.27...29
-
OA
-
OB
-
OC
OD
-
OD
Name: Basis
KEB COMBIVERT F5
Functional Description
do.25...do.32
do.33...do.40
1
1
2
1
4
1
8
1
16
1
32
1
64
1
1
128
Function
O1
Transistor output
O2
Transistor output
R1
Relay output
R2
Relay output
Internal output
Internal output
Internal output
Internal output
Date
16.04.02
1
2
4
8
8
do.41
16
32
64
128
Decimal values do.41
1
2
4
8
16
32
64
128
Chapter
Section
6
3
6
Page
17
17

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the COMBIVERT F5 BASIC and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Combivert f5 generalCombivert f5 servoCombivert f5 multi

Table of Contents

Save PDF