Network Hardware
11.1.8 Sercos Operator
00.F5.060-6000
Picture11.1.8
Sercos-Operator
COM
LWL
Diag
S-IN
Chapter
Section
Page
11
1
8
The herein described unit is a plugable operator with SERCOS-interface for the frequency
inverter or servo KEB COMBIVERT F5. As far as possible the hard and software were
developed taking the DIN/EN 61491 into consideration. The voltage supply is made by
the inverter and as an independend external supply it can be made via the terminal
strip of the inverter. The SERCOS-interface is designed as optical fibre ring for plastic
(POF) or fibre glas cable (HCS) with F-SMA plugs. The SERCOS-service channel as
well as cyclic data transfer are available. Parallel to SERCOS-operation the operation
via integrated display/keyboard and also an additional serial interface for diagnosis /
parameterization (KEB COMBIVIS) is possible (depending on the operation mode
it may be disabled). SERCOS-operation parameters like slave address, transmitting
power etc. can be adjusted via the keyboard.
START
FUNC.
ENTER
F/R
SPEED
STOP
ANTRIEBSTECHNIK
S-OUT
Date
Name: Basis
10.04.02
KEB COMBIVERT F5
COM (green)
Lights up when access via the
SERCOS service channel
LWL (red)
Full brightness : no SERCOS-input
signal (LWL disconnected, previous
device switched off)
Low brightness: receive distortion of
the SERCOS input signal (transmitting
power of the previous device too high
or too low, incorrect baud rate)
E
E (red)
on => Inver ter/Servo ready for
operation
blinking => Inverter/Servo in error
off => No supply voltage
Diag
Diagnostic interface to the PC
S-IN
SERCOS-input interface
S-OUT
SERCOS-output interface
©
Networks