Summary
Inverter Size
Housing size
Phases
Output nominal power
Max. rated motor power
Output nominal current
1)
Max. short time current
OC-tripping current
Nominal input current
Max. permissible mains fuse (inert)
Rated operating frequency
Max. operating frequency
Power loss at nominal operating
2)
Stall current at 4kHz
Max. heat sink temperature TOH
3)
Motor line cross section
4)
Min. braking resistor
4)
Typ. braking resistor
Max. braking current
Overload curve
Tightening torque for terminals
5)
Mains voltage
Mains frequency
Output voltage
Output frequency
Max. shielded motor line length
Storage temperature
Operating temperature
Model / protective system
Relative humidity
EMC tested according to product standard
Climatic category
1) With the regulated systems F5-M as well as F5-S 5% are to be subtracted as control reserve.
2) Max. current before the responding of the OL2-function (only F5-M; F5-S; F5-A)
3) Recommended minimum cross section for rated power and a cable length of upto 100m (copper)
4) This data is only valid for units with internal brake transistor GTR 7 (see "unit identification")
5) At mains voltage ≥ 460V multiply the nominal current with factor 0,86.
Chapter
Section
Page
2
1
10
25
U
3
[kVA]
145
[kW]
110
[A]
210
[A]
263
[A]
315
[A]
231
[A]
315
[kHz]
4
[kHz]
8
[W]
2300
[A]
210
[°C]
[mm²]
95
[Ohm]
[Ohm]
[A]
[Nm]
[V]
305...500 ±0 (400 V Nominal voltage)
[Hz]
[V]
[Hz]
[m]
[°C]
[°C]
max. 95% without condensation
3K3 in accordance with EN 50178
Date
Name: Basis
10.04.02
KEB COMBIVERT F5
26
27
U
U
3
3
173
208
132
160
250
300
313
375
375
450
275
330
400
450
4
2
8
8
2800
3100
250
240
90
120
150
4
4
200
2
25
50 / 60 +/- 2
3 x 0...U Mains
see Control board
50
-25...70 °C
-10...45 °C
IP20
EN 61800-3
©
Product Description
KEB Antriebstechnik, 2002
All Rights reserved
Need help?
Do you have a question about the COMBIVERT F5 BASIC and is the answer not in the manual?