10.12.18 Connecting a Monitoring Cable to a Point Water Sensor

Prerequisites
Context
When connecting the point water sensor and the CCU collector, you need to perform the
following steps to prepare a special monitoring cable.
Figure 10-55
Figure 10-55 Point water sensor
Procedure
Step 1 Connect the monitoring cable to the collector.
Table 10-60 Connecting cables to the point water sensor
Wiring Terminal in the ALM_IN Port
12 V
G
+
-
Issue 02 (2015-06-30)
A monitoring cable required has been prepared.
You are familiar with the functions of all ports on the CCU collector by referring to
10.12.2 Port Description for the CCU
You are familiar with the functions of all ports on the ECC collector by referring to
10.12.3 Port Description for the ECC
shows a point water sensor.
If connected to a CCU collector, the monitoring cable should be connected by
performing the following steps.
a.
Prepare an RJ45 connector on one end of the network cable by following the
instructions in
10.12.1 Preparing a Monitoring Cable
to the Ethernet port on the water detector.
b.
Use core wires 3, 6, 7, and 8 on the other end of the network cable as cord end
terminals and connect them to the ALM_IN port on the CCU collector, as described
in
Table
10-60.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Collector.
Collector.
and connect the network cable
Core Wire in the Cord End Terminal
Core wire 3 (green-white)
Core wire 8 (brown)
Core wire 7 (brown-white)
Core wire 6 (green)
10 Cable Layout
222