Huawei IDS2000 Dual-Row Aisle Containment Installation Manual page 197

Split-type skylight, old-version sliding door
Hide thumbs Also See for IDS2000 Dual-Row Aisle Containment:
Table of Contents

Advertisement

IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
Configuration 16
Configuration 16 applies to the scenario where the actual total power is greater than 24 kW
but no greater than 36 kW, and the backup time is 30 minutes. The following table describes
battery cabinet configuration.
Table 10-17 Battery cabinet configuration 16
Component
Battery
Battery tray
Circuit breaker
Battery cable
Figure 10-41 Conceptual diagram of battery cable connections
Issue 02 (2015-06-30)
Configuration
Rechargeable Battery 288
V-150 Ah Battery
Battery tray for 4 batteries
Circuit breaker, 690 V AC,
250 A, 3P, 36 kA/415 V
AC, 105
(W)*150(D)*102(H)
Battery Accessory, SD-288
V 150 Ah/12 V-PX-35
(OT), Battery Cabinet
Installation, 600 mm
(W)*1100 mm (D)*2000
mm (H), Top out, Cables for
battery group SHOTO
6-GFM-150 embedded in
battery cabinet of IDC (35
2
mm
), IDC special
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10 Cable Layout
Configuration Number
A string of 24 batteries
12 PCS
1 PCS
1 PCS