Huawei IDS2000 Dual-Row Aisle Containment Installation Manual page 274

Split-type skylight, old-version sliding door
Hide thumbs Also See for IDS2000 Dual-Row Aisle Containment:
Table of Contents

Advertisement

IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
BOM
Number
14170166
25030861
14170165
14170167
25030865
14170162
14170164
25030862
14170164
14170166
25030866
14170160
14170163
25030863
14170163
Issue 02 (2015-06-30)
BOM Description
Naked Crimping Terminal, DT, 50
2
mm
, M12, 200 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
2
V, ZA-YJV, 70 mm
, Black (5 Cores:
Yellow, Green, Red, Blue, Black), 269
2
A, 4x70 mm
+1x35 mm
Naked Crimping Terminal, DT, 70
2
mm
, M12, 260 A, Tin Plating
Naked Crimping Terminal, DT, 35
2
mm
, M10, 170 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
2
V, ZA-YJV, 185 mm
, Black (5
Cores: Yellow, Green, Red, Blue,
Black), 506 A, 4x185 mm
Naked Crimping Terminal, DT, 185
2
mm
, M16, 500 A, Tin Plating
Naked Crimping Terminal, DT, 95
2
mm
, M12, 320 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
2
V, ZA-YJV, 95 mm
, Black (5 Cores:
Yellow, Green, Red, Blue, Black), 328
2
A, 4x95 mm
+1x50 mm
Naked Crimping Terminal, DT, 95
2
mm
, M12, 320 A, Tin Plating
Naked Crimping Terminal, DT, 50
2
mm
, M12, 200 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
2
V, ZA-YJV, 240 mm
, Black (5
Cores: Yellow, Green, Red, Blue,
Black), 599 A, 4x240 mm
2
mm
Naked Crimping Terminal, DT, 240
2
mm
, M16, 300 A, Tin Plating
Naked Crimping Terminal, DT, 120
2
mm
, M12, 380 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
2
V, ZA-YJV, 120 mm
, Black (5
Cores: Yellow, Green, Red, Blue,
Black), 382 A, 4x120 mm
Naked Crimping Terminal, DT, 120
2
mm
, M12, 380 A, Tin Plating
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cable Position
Between the mains and the UPS
input and output PDU8000 (ATS in
a 400 A PDU8000)
2
Between the mains and the UPS
input and output PDU8000 (ATS in
a 400 A PDU8000)
2
2
+1x95 mm
Between the mains and the UPS
input and output PDU8000 (ATS in
a 500 A PDU8000)
2
Between the mains and the UPS
input and output PDU8000 (ATS in
a 500 A PDU8000)
2
+1x120
Between the mains and the UPS
input and output PDU8000 (ATS in
a 630 A PDU8000)
2
2
+1x70 mm
A Appendix
266

Advertisement

Table of Contents
loading

Table of Contents