Figure 10-19 Cabinet ground points
(1) Cabinet ground bar (optional)

10.9 Routing Signal Cables

NetEco Scenario
Figure 10-20
Issue 02 (2015-06-30)
When the equipment room area is not less than 100 m
than 100 kVA, each cabinet must be separately grounded and connected to the
equipotential bonding grid using two equipotential bonding conductors of different
length.
When the equipment room area is less than 100 m
kVA:
If cabinet ground bars are deployed, connect ground cables from servers to the
ground bars, and connect the ground bars between cabinets in sequence, which are
then connected to the ground bar in the PDU8000.
If no cabinet ground bars are deployed, connect positions 2 shown in
between the cabinets in sequence, which are then connected to the ground bar in the
PDU8000.
shows signal cable routes in the NetEco scenario.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10 Cable Layout
2
and the UPS capacity is not less
2
and the UPS capacity is less than 100
(2) Cabinet ground point
Figure 10-19