Huawei IDS2000 Dual-Row Aisle Containment Installation Manual page 183

Split-type skylight, old-version sliding door
Hide thumbs Also See for IDS2000 Dual-Row Aisle Containment:
Table of Contents

Advertisement

IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
Figure 10-29 Conceptual diagram of battery cable connections
Configuration 5
Configuration 5 applies to the scenario where the actual total power is greater than 12 kW but
no greater than 16 kW, and the backup time is 30 minutes. The following table describes
battery cabinet configuration.
Table 10-6 Battery cabinet configuration 5
Component
Battery
Battery tray
Circuit breaker
Battery cable
Issue 02 (2015-06-30)
Configuration
Rechargeable Battery 480
V-40 Ah Battery
Battery tray for 6 batteries
Circuit breaker,
Pyromagnetic Breaker, 380
V AC/500 V DC, 163 A, 4P,
36 kA, 102 (W)*70(D)*130
(H)
Battery Accessory, SD-480
V 40 Ah/12 V-PX-25 (ET),
Cables for battery group
SHOTO 6-GFM-40
embedded in battery cabinet
of IDC (25 mm
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Configuration Number
A string of 40 batteries
7 PCS
1 PCS
1 PCS
2
), IDC
10 Cable Layout
175

Advertisement

Table of Contents
loading

Table of Contents