Connecting A Monitoring Cable To A Pdu8000-0250Acv4-Sca005 - Huawei IDS2000 Dual-Row Aisle Containment Installation Manual

Split-type skylight, old-version sliding door
Hide thumbs Also See for IDS2000 Dual-Row Aisle Containment:
Table of Contents

Advertisement

IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
Figure 10-74 Wiring terminals on the TU520A ATS
Step 2 Connect the cord end terminal of the RS485 monitoring cable to the RS485 port in the
PDU8000.
the colors of core wires in the cord end terminal.
Table 10-77 Mapping between the wiring terminals in the RS485 port and the colors of core wires
in the cord end terminal
Type of the Collector
Connected
CCU collector
ECC collector
Step 3 Connect the RJ45 connector of the RS485 monitoring cable to the RS485 port on the CCU
collector or ECC collector.
----End
10.12.48 Connecting a Monitoring Cable to a
PDU8000-0250ACV4-SCA005
Prerequisites
A network cable used for monitoring has been prepared.
Issue 02 (2015-06-30)
Table 10-77
lists the mapping between the wiring terminals in the RS485 port and
Wiring Terminal in the
RS485 Port
16
17
16
17
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10 Cable Layout
Color of Core Wire in the
Cord End Terminal
Orange and white, blue
Orange, blue and white
Orange and white
Orange
249

Advertisement

Table of Contents
loading

Table of Contents