Figure 10-37 Conceptual diagram of battery cable connections
Configuration 13
Configuration 13 applies to the scenario where the actual total power is greater than 12 kW
but no greater than 24 kW, and the backup time is 15 minutes. The following table describes
battery cabinet configuration.
Table 10-14 Battery cabinet configuration 13
Component
Battery
Battery tray
Circuit breaker
Battery cable
Issue 02 (2015-06-30)
Configuration
Rechargeable Battery 288
V-65 Ah Battery
Battery tray for 4 batteries
Circuit breaker, Module
Case Circuit Breaker,
380/415 V AC, 160 A, 3P,
36 kA, C, 102 (W)*76.2
(D)*130 (H)
Battery Accessory, SD-288
V 65 Ah/12 V-PX-25 (ET),
Battery Cabinet Installation,
600 mm (W)*1100 mm
(D)*2000 mm (H), Top out,
Cables for battery group
SHOTO 6-GFM-65
embedded in battery cabinet
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10 Cable Layout
Configuration Number
A string of 24 batteries
6 PCS
1 PCS
1 PCS
185