IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
Table 3-5 Packing list of a sliding door
Name
(1) Positioning kit
(2) Glass door
(3) Lower stopper
(4) Mounting ear
(5) Upper guide rail
(6) Upper frame of a
sliding door
Procedure
Step 1 Install the sliding door mounting brackets using M5 tapping screws.
1.
Issue 02 (2015-06-30)
BOM No.
N/A
21500911
For a 2000 mm
high cabinet:
21500913
For a 2200 mm
high cabinet:
21500914
For a 2000 mm
high cabinet:
21500913
For a 2200 mm
high cabinet:
21500914
21500911
For a 2000 mm
high cabinet:
21500912
For a 2200 mm
high cabinet:
21500945
(Optional) Install sliding door mounting brackets for a 2000 mm high cabinet. Face the
aisle, and install the mounting bracket marked L on the left cabinet, and the mounting
bracket marked R on the right cabinet. Then secure the mounting brackets by installing
screws in back of the mounting brackets, as shown in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Installation Scenarios in Dual Row Aisle Containment
Quantity
4
2
2
2
1
1
Figure 3-24
Remarks
Two of the
positioning kits are
installed in the
middle of the guide
rail, and the other
two are installed at
the two ends of the
guide rail.
Packed with the
glass doors.
Can slide to the left
and right
Connects a door and
a cabinet
Connects to a
cabinet, 2000 mm
high cabinets and
2200 mm high
cabinets use
different left and
right mounting ears.
Connects to
mounting ears.
Connects a skylight
and a sliding door.
and
Figure
3-25.