BOM
Number
14170165
25030858
14170168
25030859
14170167
25030861
14170165
14170167
25030861
14170165
14170167
25030862
14170164
14170166
25030421
Issue 02 (2015-06-30)
BOM Description
Naked Crimping Terminal, DT, 70
2
mm
, M12, 260 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
2
V, ZA-YJV, 25 mm
, Black (5 Cores:
Yellow, Green, Red, Blue, Black), 138
2
A, 5x25 mm
Naked Crimping Terminal, DT, 25
2
mm
, M10, 130 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
2
V, ZA-YJV, 35 mm
, Black (5 Cores:
Yellow, Green, Red, Blue, Black), 171
2
A, 5x35 mm
Naked Crimping Terminal, DT, 35
2
mm
, M10, 170 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
2
V, ZA-YJV, 70 mm
, Black (5 Cores:
Yellow, Green, Red, Blue, Black), 269
2
A, 4x70 mm
+1x35 mm
Naked Crimping Terminal, DT, 70
2
mm
, M12, 260 A, Tin Plating
Naked Crimping Terminal, DT, 35
2
mm
, M10, 170 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
V, ZA-YJV, 70 mm^2, Black (5
Cores: Yellow, Green, Red, Blue,
Black), 269 A, 4x70 mm^2+1x35
mm^2
Naked Crimping Terminal, DT, 70
mm^2, M12, 260 A, Tin Plating
Naked Crimping Terminal, DT, 35
2
mm
, M10, 170 A, Tin Plating
Electronic|Electric Cable, 600 V/1000
2
V, ZA-YJV, 95 mm
, Black (5 Cores:
Yellow, Green, Red, Blue, Black), 328
2
A, 4x95 mm
+1x50 mm
Naked Crimping Terminal, DT, 95
2
mm
, M12, 320 A, Tin Plating
Naked Crimping Terminal, DT, 50
2
mm
, M12, 200 A, Tin Plating
Power Cable, 300/500 V, 60227IEC10
2
(BVV), 3x2.5 mm
, Black (Cores:
Blue, Brown, Yellow/Green), 27 A,
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cable Position
Between the 100 A PDU8000 and
the precision power distribution
cabinet
Between the 125 A PDU8000 and
the precision power distribution
cabinet
Between the 160 A/200 A
PDU8000 and the precision power
distribution cabinet
2
Two power cables between the 200
A PDU8000 and the precision
power distribution cabinet
Two power cables between the 250
A PDU8000 and the precision
power distribution cabinet
2
Power cable for the single-phase 16
A (3.5 kW) PDU2000
A Appendix