IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
When securing the skylight connective plate to the cabinet, partially tighten the screws so
that you do not have to remove the screws if the skylight cannot be accurately mounted.
Fully tighten the screws after the skylight is accurately mounted.
Skylight connective plates used for the control skylight have no skylight mounting
brackets.
Ensure that the middle point on the width side of the skylight connective plate aligns with
the middle point on the width side of the cabinet, and the plate panel is on the same plane
as the front beam of the cabinet.
Issue 02 (2015-06-30)
Figure 3-7 Installing a skylight connective plate
If certain air conditioners or UPS cabinets have no M12 tapped holes at the top,
secure the skylight connective plate to the top of the cabinet using a socket wrench
and M8 bolts, as shown in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Installation Scenarios in Dual Row Aisle Containment
Figure
3-8.