Connecting The Pe Cable - Huawei SUN2000-M3 User Manual

Table of Contents

Advertisement

SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual
No.
4
Note a: Five-core cables with a cross-sectional area of 5 x 35 mm
mm
If the SUN2000 is used with an optimizer, route the AC and DC power cables
separate to avoid interference to the communication of the optimizer.

5.3 Connecting the PE Cable

● Ensure that the PE cable is securely connected. Otherwise, electric shocks may
occur.
● Do not connect the neutral wire to the enclosure as a PE cable. Otherwise,
electric shocks may occur.
Procedure
Step 1 Crimp OT terminals.
● Avoid scratching the core wire when stripping a cable.
● The cavity formed after the conductor crimp strip of the OT terminal is crimped
must wrap the core wires completely. The core wires must contact the OT
terminal closely.
● Wrap the wire crimping area with heat shrink tubing or PVC insulation tape.
The heat shrink tubing is used as an example.
● When using a heat gun, protect devices from being scorched.
Issue 11 (2023-01-10)
Cable
Type
PE cable
Single-core outdoor
copper-core cable
2
are not supported.
NO TICE
D ANGER
NO TE
● The PE point at the AC output port is used only as a PE equipotential point, not a
substitute for the PE point on the enclosure.
● It is recommended that silicone sealant or paint be applied around the ground terminal
after the PE cable is connected.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
Recommended
Specifications
Conductor cross-
sectional area ≥ 16
2
mm
2
or 5 x 50
Source
Prepare
d by
users
37