Connecting A Monitoring Cable To A Wcon-14Z Skylight Ceiling Controller - Huawei IDS2000 Dual-Row Aisle Containment Installation Manual

Split-type skylight, old-version sliding door
Hide thumbs Also See for IDS2000 Dual-Row Aisle Containment:
Table of Contents

Advertisement

IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10.12.10 Connecting a Monitoring Cable to a WCON-14Z Skylight
Ceiling Controller
Prerequisites
Context
Table 10-51
Table 10-51 Ports on the skylight controller
Port
12 V+
G-
C
NO
MANUAL, REMOTE
SOUND (12 V+ G-)
1 (+ -) to 14 (+ -)
POWER ALM
SMG ALM
Issue 02 (2015-06-30)
A monitoring cable required has been prepared.
You are familiar with the functions of all ports on the CCU collector by referring to
10.12.2 Port Description for the CCU
You are familiar with the functions of all ports on the ECC collector by referring to
10.12.3 Port Description for the ECC
describes the ports on the skylight controller.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Collector.
Collector.
Function
Connects to a smoke sensor.
Connects to a smoke sensor.
Connects to a smoke sensor.
Connects to a smoke sensor.
Connects to the CCU or
ECC, controlling the
opening of the skylight.
Connects to an audible and
visual alarm.
Connects to a skylight
magnetic lock.
Connects to a CCU or an
ECC, the power alarm is
reported over dry contacts.
Connects to a CCU or an
ECC. A smoke sensor alarm
10 Cable Layout
Remarks
Configuration on the
NetEco is not required.
Configuration on the
NetEco is not required.
Configuration on the
NetEco is not required.
Configuration on the
NetEco is not required.
Controls signals and the
opening of the skylight.
Configuration on the
NetEco is not required.
The audible and visual
alarm generates an alarm
when the system is faulty.
Configuration on the
NetEco is not required.
The electromagnet is
powered on and the skylight
is opened when 12 V power
is normally supplied.
Configuration on the
NetEco is not required.
Available when closed. Set
the port on the NetEco to
report low level alarms over
a dry contact.
Available when closed. Set
the port on the NetEco to
211