Installing Sealing Components In The Scenarios With A Column; Installing Sealing Plates And Skylight Connective Plates - Huawei IDS2000 Dual-Row Aisle Containment Installation Manual

Split-type skylight, old-version sliding door
Hide thumbs Also See for IDS2000 Dual-Row Aisle Containment:
Table of Contents

Advertisement

IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
4.3 Installing Sealing Components in the Scenarios with a
Column

4.3.1 Installing Sealing Plates and Skylight Connective Plates

Context
If a column exists between cabinets and the aisle and a cabinet cannot be installed in the space
near the column, you need to install sealing plates. There are different types of sealing plates.
Choose appropriate ones depending on the column size and installation policy.
Table 4-2 Types of sealing plates
Sealing Plate
300 mm wide, 2000 mm high sealing plate
300 mm wide, 2200 mm high sealing plate
600 mm wide, 2000 mm high sealing plate
600 mm wide, 2200 mm high sealing plate
800 mm wide, 2000 mm high sealing plate
800 mm wide, 2200 mm high sealing plate
Procedure
Step 1 Apply a sealing rubber strip to the side of the sealing plate that is near the cabinet, and then
install the sealing plate close to the column. If there is no cabinet on the side opposite the
column, you also need to install a sealing plate and align it with the adjacent skylight side
panel.
The flanges on the sealing kit are against the pillar.
Step 2 Secure the skylight connective plate to the sealing plate or cabinet using bolts.
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Installation Scenarios with Pillars
BOM No.
21500707
21500939
21500718
21500940
21500720
21500941
77