Huawei IDS2000 Dual-Row Aisle Containment Installation Manual page 261

Split-type skylight, old-version sliding door
Hide thumbs Also See for IDS2000 Dual-Row Aisle Containment:
Table of Contents

Advertisement

IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
Cable Installation Check
Table 11-2 Cable installation check items
No.
1
2
3
4
5
6
7
8
Electrical Installation Check
Table 11-3 Electric installation check items
No.
1
2
3
4
Issue 02 (2015-06-30)
Check Whether
All cable joints are secured properly,
especially the cable joints between
network cables.
Exposed parts near the wiring
terminals and lugs are wrapped in PVC
insulation tape or heat shrinking
tubing.
The flat washers and spring washers of
all wiring terminals are securely
installed.
Cables are bound neatly and cable ties
are secured evenly and properly.
Routed cables should be convenient for
future maintenance and expansion.
All labels at the cable ends are clear.
The excess section of a cable strip is
cut evenly.
There are no unnecessary adhesive
tape or cable ties on cables.
Check Whether
All ground cables are copper cables.
Cable diameters are correct. No
switches or fuses are installed on the
cables and no short circuit occurs.
The ground cable, AC power cables,
and internal cables are correctly
connected and screws are secured. No
short circuit occurs during power input
or output.
The length of ground cables and power
cables is correct.
Lugs for power cables and PGND
cables are soldered or crimped
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
11 Check after Installation
Check Result
□Passed. □Failed.
□Passed. □Failed.
□Passed. □Failed.
□Passed. □Failed.
□Passed. □Failed.
□Passed. □Failed.
□Passed. □Failed.
□Passed. □Failed.
Check Result
□Passed. □Failed.
□Passed. □Failed.
□Passed. □Failed.
□Passed. □Failed.
253