Huawei IDS2000 Dual-Row Aisle Containment Installation Manual page 234

Split-type skylight, old-version sliding door
Hide thumbs Also See for IDS2000 Dual-Row Aisle Containment:
Table of Contents

Advertisement

IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
Procedure
Step 1 Connect the monitoring cable to the collector.
Table 10-62 Core wires of the electronic door lock
Color
Red
Black
Blue
Green
Cut off the crystal connector from as near the connector as possible.
Table 10-63 Matches by core wire colors
Electronic Door Lock
Red
Black
Blue
Green
----End
Issue 02 (2015-06-30)
You are familiar with the functions of all ports on the ECC collector by referring to
10.12.3 Port Description for the ECC
If connected to a CCU collector, the monitoring cable should be connected by
performing the following steps.
a.
Cut off the crystal connector on the monitoring cable for the electronic door lock.
Table 10-62
describes the core wires of the electronic door lock.
b.
Cut off one end of the network cable.
c.
Connect the core wires of the electronic door lock to the network core wires by
sequence specified in
d.
Connect the other end of the network cable to the RS485 port on the CCU collector.
If connected to an ECC collector, connect the RJ45 connector of the electronic door lock
cable to the RS485 port on the ECC collector.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Collector.
Function
Positive power terminal
Negative power terminal
RS485+
RS485-
Table
10-63.
Network cable
Green and white
Brown
Orange-white, and blue
Orange, and blue-white
10 Cable Layout
226